Can an AC drive be used on a 2-speed motor?
Issue:
Wanting to use an AC drive on a 2-speed motor.
Product Line:
Altivar drives
Environment:
All
Cause:
N/A
Resolution:
Yes.
The motor should be connected to the drive with the high speed windings. It is not necessary to use the low speed windings when connected to an AC drive.
It is important to consider the motor full load amp rating when selecting the appropriate drive for the application. The high speed winding is likely the higher rating on the motor nameplate.
Wanting to use an AC drive on a 2-speed motor.
Product Line:
Altivar drives
Environment:
All
Cause:
N/A
Resolution:
Yes.
The motor should be connected to the drive with the high speed windings. It is not necessary to use the low speed windings when connected to an AC drive.
It is important to consider the motor full load amp rating when selecting the appropriate drive for the application. The high speed winding is likely the higher rating on the motor nameplate.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.