What is the largest branch breaker that mounts on the NQOD bus?
Issue:
Largest branch breaker that can be mounted on the NQOD bus
Product Line:
NQOD Panelboard
Environment:
Products sold and used in the United States
Cause:
Installation / Setup
Resolution:
The largest branch breaker for an NQOD panel is 150 amps using the QOB-VH frame. Use the following:
For 2 pole, order QOB2150VH which uses 4 pole spaces
For 3 pole, order QOB3150VH Which uses 6 pole spaces