Will the NetBotz Fluid Detector (FD100 or NBES0301) detect 100% pure water?
Issue:
Will the NetBotz Fluid Detector (FD100 or NBES0301) detect 100% pure water
Product Line:
NetBotz
Environment:
NetBotz fluid detectors NBES0301 and NBFD0100
Cause:
Fluid detectors work using conductivity. Pure water is not conductive enough to sense.
Resolution:
The NetBotz Fluid Detector will detect distilled water but not 100% pure water.
However, the NetBotz Fluid Detector will probably work in most environments as the minute pure water makes contact with any impure surface (metal pans, floors, etc..) it will pickup ions and should immediately become conductive.
Will the NetBotz Fluid Detector (FD100 or NBES0301) detect 100% pure water
Product Line:
NetBotz
Environment:
NetBotz fluid detectors NBES0301 and NBFD0100
Cause:
Fluid detectors work using conductivity. Pure water is not conductive enough to sense.
Resolution:
The NetBotz Fluid Detector will detect distilled water but not 100% pure water.
However, the NetBotz Fluid Detector will probably work in most environments as the minute pure water makes contact with any impure surface (metal pans, floors, etc..) it will pickup ions and should immediately become conductive.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Продукт:
Досліджуйте більше
Серія:
Продукт:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.