Can an ATV212 drive's programming be saved to the HMI keypad (VW3A1101)?
Issue:
Can I store the ATV212 program in the HMI VW3A1101?
Product Line:
Altivar ATV212
Environment:
All model numbers, all serial numbers
Cause:
N/A
Resolution:
No, the ATV212's programming cannot be saved to any of the keypads available.
Programming can be saved by any of three methods:
- in the drive by setting parameter tYP = 7
- in the Multiloader tool
- by using SoMove software