How to change the display on an ATV212 drive to show 0-100% instead of 0-60hz range?
Issue:
Changing the display on an ATV212 drive to show 0-100% instead of 0-60hz range.
Product line:
Altivar 21, Altivar 212, ATV21, ATV212, S-Flex
Environment:
All models and all serial numbers.
Cause:
The drive originally is setup to output Hz on the main screen.
Resolution:
In order to display a percentage value instead of Hz:
Changing the display on an ATV212 drive to show 0-100% instead of 0-60hz range.
Product line:
Altivar 21, Altivar 212, ATV21, ATV212, S-Flex
Environment:
All models and all serial numbers.
Cause:
The drive originally is setup to output Hz on the main screen.
Resolution:
In order to display a percentage value instead of Hz:
- From '0.0' or 'OFF' (whichever your drive may display while waiting for run command), press the Mode button once until you see 'AUF'
- Press the down arrow button until you see the F--- submenu and press ENT
- Hold down the down arrow until you see F702 and press ENT
- Provide a value of 1.67 to convert 60 Hz to 100 percent.
- Press ENT again to save the change
- Press Mode a couple times until you're back out to '0.0' or 'OFF'
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.