What is the part number for the ATV71HC11N4 and ATV61HC13N4 power boards?
Issue:
Needs a Power board for ATV71HC11N4
Product line:
ATV71 and ATV61
Environment:
All models, all serial numbers
Cause:
Power board not functional
Resolution:
The Power board for these drive is VX5A1HC1113.
It is required to check the Serial number of the drive before ordering the Power Board.
If the 8th digit in the serial number is 2, the drive was built using Fuji IGBT's instead of the standard Mitsubishi IGBT's. A drive with Fuji IGBT's requires a modified version of the Power board (VX5A1HC1113F). IGBT, and gate driver board parts also will have an F at the end.
Needs a Power board for ATV71HC11N4
Product line:
ATV71 and ATV61
Environment:
All models, all serial numbers
Cause:
Power board not functional
Resolution:
The Power board for these drive is VX5A1HC1113.
It is required to check the Serial number of the drive before ordering the Power Board.
If the 8th digit in the serial number is 2, the drive was built using Fuji IGBT's instead of the standard Mitsubishi IGBT's. A drive with Fuji IGBT's requires a modified version of the Power board (VX5A1HC1113F). IGBT, and gate driver board parts also will have an F at the end.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.