How does the high head pressure protection feature work on the ACSC?
Issue:
How does the high head pressure protection feature work?
Product line:
ACSC100, ACSC101
Environment:
InRow Cooling
Cause:
Resolution:
The unit targets a refrigerant condensing pressure of 425 psig (29.3 bar) and the condenser fans modulate to maintain this. The high head pressure switch trip limit is 550 psig (37.9 bars). When condensing pressure reaches 520 psig (35.8 bars), the controller slows the evaporator fans down and opens the electronic hot gas bypass valve to reduce condensing pressure.
How does the high head pressure protection feature work?
Product line:
ACSC100, ACSC101
Environment:
InRow Cooling
Cause:
Resolution:
The unit targets a refrigerant condensing pressure of 425 psig (29.3 bar) and the condenser fans modulate to maintain this. The high head pressure switch trip limit is 550 psig (37.9 bars). When condensing pressure reaches 520 psig (35.8 bars), the controller slows the evaporator fans down and opens the electronic hot gas bypass valve to reduce condensing pressure.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.