Why is the CB status of Sepam Series 40 displayed with ‘?’ mark in PowerLogic SCADA?

If you have a problem as per below, you need to check 2 things.

a. The hard-wired signals from the CB which are for CB On/Off status must be connected to Sepam 40 following the default IO setting. (Please take a Sepam 40 manual for more details.)

b. Device closed tag must be added into your project.

You can find this tag under Sepam Series 40 with default IO device type -> Miscellaneous -> Real Time Tags in PowerLogic SCADA Profile Editor.

Check also last Updated information from our PowerLogic L3 Team

Key words and phrases:

question mark, meaning, signification, signify, mean, what

AEBL3

Original Author: YJ

Public

All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL200477 V2.0, Originally authored by KBAdPM on 11/11/2009, Last Edited by DaMi on 01/22/2010
Related ranges: Sepam series 40, PowerLogic SCADA 7.1

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings