Is it possible adjust the nominal current of an ATS48C41Y below 0,4 IcL?

Issue:

Is it possible adjust the nominal current of an ATS48C41Y below 0,4 IcL?

Product Line:

ATS48

Resolution:

It's not possible to modify the soft-starter by replacing the control board because there is an EEPROM inside the power board containing the size ( nominal current, etc... ) and there is an auto-adaptation between both cards. The thermal protection is made with PTC on the heatsink and calculation with the thyristors. The best solution is to replace the ATS to a smaller size.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Продукт:
Серія:
Досліджуйте більше
Продукт:
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Спільнота Schneider Electric
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings