Why do I receive the error "Incompatibility between the dropped module and the last module of segment 1", when trying to add a module following the STBCPS2111 Auxilliary Power Supply?

Issue:

Why do I receive the error "Incompatibility between the dropped module and the last module of segment 1", when trying to add a module following the STBCPS2111 Auxilliary Power Supply?

Product Line:

STBCPS2111 Auxilliary Power Supply

Resolution:

The reason this error is received is because when a STBCPS2111 Auxilliary Power Supply is added to the segment it has to be followed by a PDM module and then add a compatible IO module.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.