Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Reporter generates Automation Error in pmlRepGen

Goals and Symptoms

Reporter shows automation error in PML Repgen
Report Status
Error reads:

  • Error -2147221080 (Automation error) has occurred in pmlRepGen

Causes and Fixes

This can be caused by incorrect database rights:

  1. Open SQL Management Console and expand the tree down to ION_Data > Users.
  2. In the right hand pane double click on Report to show properties.
    SQL user properties
  3. It should only have Public, db_datareader and ION_Reader checked.
  4. If you need to alter this cancel out of the above screens and expand the tree in the left hand pane and go to Security > Logins.
  5. Double click Reports in the right hand pane > Database Access tab> now edit the database role (to allow the three access rights mentioned in step #3).
    SQL properties

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings