Can we use Aluminium cable ?
Goals and Symptoms
Can we use Aluminium cable ?
Facts and Changes
AB1VVN7035U
Causes and Fixes
It is not recommended to used our terminal block type AB1VVN with alu-cable because it is necessary to check regularly the tightening torque.
You can used alu cable but it is necessary to respect some rules.
1. After removing the insulation of the alu-cable, clean the alu cable and treat it with a grease in order to avoid oxidation.
2. alu cable must be tighten with a torque higher than the nominal tightening torque. ( 65%, 10Nm)
3. It is necessary to tighten again the cable 15 days after the installation.
Then, check the tightening torque 1 or 2 times per years ( depend on the application )
4. The maximum current must be 60% of the nominal current.
Legacy KB System (APS) Data: RESL198038 V1.0, Originally authored by LaBe on 03/14/2009, Last Edited by LaBe on 03/14/2009
Related ranges: AB1, DB6