Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Can ION meters use the same set CTs and PTs with multiple meters?

Issue
Customer would like to use the same set of Potential transformers (PTs) and/or current (CTs) multiple meters.

Product line
ION meters that require CTs/PTs

Resolution
Yes, multiple meters can use the same PTs and CTs for ION meters, but their are some things to be aware of:

  • The total burden from the current inputs of the meter must be less than the maximum burden rating of the CTs
  • If the wires between the current inputs of the meters (i.e. wire from I12 on one meter to I11 of another meter) is too long, or has a significant impedance, it may affect the overall measuring accuracy of the meters
  • Use the shortest length and largest gauge of wire possible for the CT and PT connections to limit any losses in the lines.

The below diagram is an example of a 4-Wire Wye, 3 Element diagram.

Wiring diagram

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings