Loading settings onto a VAMP relay that doesn't have the same complete part number.

Issue

Can the settings file from a VPG210‑001361 relay be directly loaded into a VAMP 210‑5A7ADA‑3.20 relay using VAMPset?

Product

VAMP relays

Environment

VAMPset configuration software
VAMP 200‑series and 210‑series relays
Settings file compatibility
Part number and firmware validation

Cause

VAMP relays rely on their complete part number and firmware version to determine feature sets, hardware options, and supported configuration parameters. Differences in part numbers or firmware versions make setting files incompatible and may lead to functional mismatch or errors.

Resolution

A settings file cannot be loaded into a VAMP relay if the complete part numbers do not match exactly. Each relay with a different part number must be manually configured to ensure proper operation.

Additionally, even if the part numbers match, the settings file cannot be loaded if the firmware versions are different. In such cases, settings must be recreated manually or the firmware must be aligned before attempting to load the file.

Schneider Electric Україна

Досліджуйте більше

Досліджуйте більше

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.