Data Center Expert | Why does StruxureWare not accept my One Time passcode?
Issue
StruxureWare Data Center Expert is not accepting my One Time passcode.
Product Line
StruxureWare Data Center Expert (DCE)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)
StruxureWare Central (SWC)
InfraStruXure Central (ISXC)
Environment
StruxureWare Data Center Expert (all versions)
StruxureWare Central (all versions)
InfraStruXure Central (all versions)
Cause
SturuxureWare / EcoStruxure Data Center Expert requires a 64 character license key that is created at EcoStruxure IT Entitlements portal at https://ecostruxure-it-entitlements.se.com/ by combining the passcode and the Data Center Expert's MAC address.
Resolution:
The Passcode you receive when purchasing a license key is not the actual license.
Below you will find instructions to convert the passcode to a license key.
1. In a web browser, navigate to EcoStruxure IT Entitlements portal at https://ecostruxure-it-entitlements.se.com/
2. Log in to the site using e-mail and password or register.
3. Follow the instructions located on the Welcome page.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.