Чим ми можемо вам допомогти сьогодні?

How to get the Magelis/Harmony HMI to read a KollMorgen AKD Servo Drive low 32bit word that is 64bit word in the drive?

Issue:
How to get the Magelis/Harmony HMI to read a KollMorgen AKD Servo Drive low 32bit word that is 64bit word in the drive?

Product Line:
XBTG/GH/GK/GT, Smart iPC, Compact iPC, HMIGTO/GTU/STO/STU

Environment:
Modbus Addressing

Resolution:
To resolve the issue you need to go into the Workbench Software(the AKD configuration software) change the drive parameters scale from “MODBUS Scaling"
to “Drive internal”.  (See screenshot below).  The value will come into the Magelis as a double integer, you will need to divide by 1000 to get the correct value.

screenshot

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше

Досліджуйте більше

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.