Is there a replacement for Schneider Electric's ATVPOT25K speed potentiometer for Altivar drives?
Issue:
ATVPOT25K speed potentiometer obsolete replacement for Altivar drives
Product Line:
Altivar Machines
Environment:
All models and serial numbers
Cause:
Selection of Speed Potentiometer for speed control
Resolution:
Altivar VFD's can use a speed potentiometer from 5K ohms to 10K ohms.
Suggest using one of the following:
For 22mm
Metal - XB4BD912R10K
Plastic - XB5AD912R10K
For 30mm
Metal - 9001K2108
Plastic - 9001SK2108
ATVPOT25K speed potentiometer obsolete replacement for Altivar drives
Product Line:
Altivar Machines
Environment:
All models and serial numbers
Cause:
Selection of Speed Potentiometer for speed control
Resolution:
Altivar VFD's can use a speed potentiometer from 5K ohms to 10K ohms.
Suggest using one of the following:
For 22mm
Metal - XB4BD912R10K
Plastic - XB5AD912R10K
For 30mm
Metal - 9001K2108
Plastic - 9001SK2108
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.