Чим ми можемо вам допомогти сьогодні?
Video: How to Save and Upload Meter Templates from One Device to Another Using ION Setup.
Issue:
Need to make meter configuration on two devices virtually identical.
Product Line:
ION 73xx, 75xx, 76xx, 8300, 8400, 8500, 86xx, 9000 series
PM 5xxx, 8000 series
ION Setup
Environment:
ION Setup
Cause:
Meter is aging and needs replaced/ updated, or custom functionality has been programmed in one device and is needed in all installed devices.
Resolution:
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
You can copy (Save to PC) a configuration from one meter
and paste (Send to Meter) it to another meter of the same type using ION Setup.
Open ION Setup and connect to the original meter with the intended program.
In the Setup Assistant, click the Template setup screen on the left as illustrated below.
This screen has four tabs:
- Save to PC lets you save a device configuration file (.dcf) containing custom
configuration changes. You can make custom changes to one meter, upload the
configuration file onto a workstation, and then download this file onto one or
more other meters. You can only download the .dcf file to other meters of the
same type.- NOTE Uploading or retrieving device configuration may take some time. If you abort the procedure, ION Setup
provides you with a list of the copy procedures that were successfully completed before they were stopped.
- NOTE Uploading or retrieving device configuration may take some time. If you abort the procedure, ION Setup
- Send to Meter lets you download to other meters a configuration file you have
created or uploaded. The following formats are supported:- ION Setup device configuration file (.dcf)
- ION Enterprise framework file (.fwn)
- NOTE Framework (.fwn) files created in PEGASYS software are not supported.
- Firmware upgrade lets you upgrade the meter to gain access to new or
enhanced ION modules. When you perform a firmware upgrade, you are
prompted to download the configuration file onto the meter. See the Upgrading
PowerLogic ION Device Firmware technical note for more information on
upgrading your device’s firmware. - Register Edit lets you to view and modify energy register values.
Template Paste Options
Some modules are not copied when upgrading firmware, saving to PC or sending
to a meter. The setup registers of the following modules remain intact and must be
configured manually:
- Communications modules Security Option modules
- Security User modules
- Log Mail modules
The Template Paste Options screen also allows you the option of retaining PT/CT, Clock/Nameplate settings and Energy Readings.
- PT/CT Settings retains your setup registers for Power Meter modules.
- Clock Settings retains your setup registers for the clock module.
- Nameplate Settings retains your Owner, Tag1 and Tag2 settings.
- Energy Readings retains the integrator values from your energy registers.
- ITC Settings retains your instrument transformer correction settings.
Communication settings may now need to be applied manually to fully replace original meter.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.