Чим ми можемо вам допомогти сьогодні?

What is the purpose of the external battery of the M221?

The help content gives us the information that the battery of the M221 allows:
- to save the content of the whole %MW area ( %MWi with i>50;  note: %MW0-%MW49 are also save without battery)
- to save the RTC clock

In reality the battery is always needed/mandatory because without battery the PLC can’t start in RUN after a Power Cycle.
Within %S75 the PLC program can check when the battery has the be replaced before it becomes out of order (average is every 4/5 years):
=> when this bit is Set to 1, it means the external battery power is low and it has to be replaced soon.

Note:

This info is valid for the versions prior to SoMachine Basic - V1.3 SP1 - build 44532 and Functional level lower than V3.1.

From SoMachine Basic - V1.3 SP1 and with the Functional level V3.1, a new Starting mode is available:

Unconditional Start In Run : The logic controller automatically starts application execution even if the controller battery is absent or discharged.

Unconditional Start in Run

Schneider Electric Україна

Досліджуйте більше

Серія:

Досліджуйте більше

Серія:

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.