How many Remote IO drops does an M580 PLC support?

Article available in these languages:

  • Spanish

Issue:

How many Remote IO drops does an M580 PLC support?

Product Line:

M580

Resolution:

M580 CPU                      |        Max Remote I/O Drops
--------------------------------------------------------------------------------

BME P58 2040                |              8
BME P58 3040                |              16
BME P(H)58 4040           |              16
BME P(H)58 5040           |              31
BME P(H)58 6040           |              31
--------------------------------------------------------------------------------
A "Rack" is defined as a backplane which holds devices.
A "Drop" is defined as the rack which are connected to CPU as a node on the RIO network.
A Drop can contain multiple racks by use of the BMXXBE Rack Extenders.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings