Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Synchronization of a PLC application and Web designer application using .XVM file
Issue
All changes in  Unity PRO will require a synchronization between Unity and the WMY module. Synchronization can be accomplished by using the .stu file and .xvm file. In some case the synchronization using .STU file takes longer and therefore using a .XVM file is more efficient.


Product Line

Factory cast HMI (WMY, NMW)

Resolution

Below the steps on .xvm synchronization:

After rebuilding and saving Unity PRO:

Export “Variable & FB Instances” as .XVM






On Web Designer, “Import PLC Symbols”, import the up-to-date .XVM file to the Device0.




Transfer the up-to-date Web Designer project to the target WMY100  (PC->Target)


When prompted to reboot module, click “Yes”.

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Спільнота Schneider Electric
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings