What are the voltage, temperature and altitude tolerances for the Altivar 32/320 drive?
Issue:
Customer wants to know the temperature and altitude limitations for the ATV32/ATV320 drive.
Product line:
ATV32, Altivar 32, ATV320, Altivar 320
Environment:
All
Cause:
n/a
Resolution:
The voltage range for the M2 drives (200-240V) is 200V, minus 15% to 240V, plus 10%.
The voltage range for the N4 drives (380-480V) is 380V, minus 15% to 480V, plus 15%.
The temperature rating for all models is +14F to +122F (-10C to +50C), without derating (as long as the switching frequency is 4 kHz or less).
Optional derating is available from +122F to +140F (50C to 60C). Consult the Installation manual for de-rating curves based on the temperature and switching frequency.
The maximum altitude the Altivar 32 can be installed without de-rating is up to 3300 feet (1000 meters). De-rate the drive nominal current by each additional 330 feet (100m) up to a maximum ceiling of 10,000 feet (3000m).
Customer wants to know the temperature and altitude limitations for the ATV32/ATV320 drive.
Product line:
ATV32, Altivar 32, ATV320, Altivar 320
Environment:
All
Cause:
n/a
Resolution:
The voltage range for the M2 drives (200-240V) is 200V, minus 15% to 240V, plus 10%.
The voltage range for the N4 drives (380-480V) is 380V, minus 15% to 480V, plus 15%.
The temperature rating for all models is +14F to +122F (-10C to +50C), without derating (as long as the switching frequency is 4 kHz or less).
Optional derating is available from +122F to +140F (50C to 60C). Consult the Installation manual for de-rating curves based on the temperature and switching frequency.
The maximum altitude the Altivar 32 can be installed without de-rating is up to 3300 feet (1000 meters). De-rate the drive nominal current by each additional 330 feet (100m) up to a maximum ceiling of 10,000 feet (3000m).
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.