Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Why would I see Output Phase Loss on my E-flex system that is equipped with Bypass (Power circuit Y)?
Issue:
Possible cause of an Output Phase Loss on an E-flex system that is equipped with Bypass (Power circuit Y)

Product Line:
8839EFD* E-flex systems.

Environment:
Units equipped with power circuit Y (Full voltage bypass)

Cause:
Customer is seeing random Output Phase Loss faults with no apparent cause.

Resolution:
Output Phase Loss faults should not be indicated on an E-flex system with Full Voltage Bypass.   Under menu 1.8, Fault management menu, Output Phase Loss should be disabled on E-flex systems, with the bypass contactor.  This should be disabled from the factory to prevent a known condition where Output Phase Fault can be improperly triggered in E-flex systems equipped with full voltage bypass contactors.  Phase loss protection for the motor is provided by other components within the E-flex system in this particular configuration.


Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings