Issue:
Line termination resistor on the ATV212 drive set up for Bacnet protocol.
Product Line:
Altivar ATV212
Environment:
All
Cause:
Needs to terminate his Bacnet line and wants to know how to set the drive up.
Resolution:
Switch SW103 is the line termination resistance switch to put 120 ohms across the data pins A and B.
Line termination resistor on the ATV212 drive set up for Bacnet protocol.