How to import SoMachine/Machine Expert - Basic symbols in Vijeo Designer?
Using SoMachine Basic in SoMachine Central
- You need to export your project as "SoMachine Basic project" (see attachment 1).
- In Vijeo designer:
- In the IO Manager, add the Modbus TCP/IP Driver and select Modbus Equipment.
- Write the IP Address of the M221 PLC and check the case IEC61131. You also need to select the Double word order (see attachment 2).
- Do a right click in "Variables”, select "Link Variables" and "*.SMPB" for file types, then select your project (see attachment 3).
- You can now select which symbols you want to import.
Using SoMachine/Machine Expert - Basic standalone
In Vijeo designer:
- In the IO Manager, add the Modbus TCP/IP Driver and select Modbus Equipment.
- Write the IP Address of the M221 PLC and check the case IEC61131. You also need to select the Double word order (see attachment 2).
- Do a right click in "Variables”, select "Link Variables" and "*.SMPB" for file types, then select your project (see attachment 3).
- You can now select which symbols you want to import.
Опубліковано для: Schneider Electric Україна
Вкладення
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.