How to program an input on the ATV12 to freewheel stop?
Issue:
Configure an ATV12 to freewheel stop
Product Line:
Altivar 12
Environment:
All serial numbers
Cause:
N/A
Resolution:
To program an input to freewheel stop on the ATV12 use the following steps from RDY:
Press enter to rEf
Turn clockwise to ConF press enter.
Turn clockwise to Full press enter.
Turn clockwise to Fun press enter.
Turn clockwise to Stt- press enter.
Turn clockwise to nSt press enter.
Select the input to use for nSt press enter.
Esc back to the beginning and cycle power.
Configure an ATV12 to freewheel stop
Product Line:
Altivar 12
Environment:
All serial numbers
Cause:
N/A
Resolution:
To program an input to freewheel stop on the ATV12 use the following steps from RDY:
Press enter to rEf
Turn clockwise to ConF press enter.
Turn clockwise to Full press enter.
Turn clockwise to Fun press enter.
Turn clockwise to Stt- press enter.
Turn clockwise to nSt press enter.
Select the input to use for nSt press enter.
Esc back to the beginning and cycle power.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.