What terminals can the speed pot be wired to on the Altivar ATV61 and ATV71 drives?
Issue:
Terminals to connect Speed Potentiometer on ATV61/71 Drives
Product Line:
Altivar ATV61 and ATV71
Environment:
All
Cause:
Needs to know where the Pot can be wired on the ATV61 or ATv71 drive.
Resolution:
The Pot will have 3 terminals The center terminal is the wiper it is wired to AI1+
1st leg is wired to +10vdc
3rd leg is wired to com that is jumpered to AI-