ATV61/ATV71 input summing. With Reference channel set to HMI, does the MFR parameter reset to default (100%) after a power cycle?
Issue:
Input summing used in ATV61/ATV71, the HMI is being used for the multiplier input (MA2). MFR is being reset to 100% after each power cycle.
Product Line:
ATV61/ATV71
Environment:
All models, All serial numbers
Cause:
Information not available in current literature.
Resolution:
Yes, the MFR parameter will be reset to 100% each time power is cycled. There is no way to save the value of MFR into EEPROM memory. To prevent this from causing a problem, try using an analog input for your multiplier instead of the HMI.
Input summing used in ATV61/ATV71, the HMI is being used for the multiplier input (MA2). MFR is being reset to 100% after each power cycle.
Product Line:
ATV61/ATV71
Environment:
All models, All serial numbers
Cause:
Information not available in current literature.
Resolution:
Yes, the MFR parameter will be reset to 100% each time power is cycled. There is no way to save the value of MFR into EEPROM memory. To prevent this from causing a problem, try using an analog input for your multiplier instead of the HMI.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.