What is ULF on the ATS48?
Issue:
ATS48 with ULF (under load fault).
Product Line:
Altistart 48
Environment:
All serial numbers
Cause:
Drive is detecting an under load fault?
Resolution:
ULF is an under load fault. The fault is caused by parameter settings on the soft starter. In the PRO menu parameter ULL (Activation of motor under load) enables the under load detection. Parameter LUL (Motor underload threshold) set the percentage of torque for the underload detection. Parameter TUL (Motor underload time), set the time delay before ULL faults when the motor torque falls below LUL threshold.
ATS48 with ULF (under load fault).
Product Line:
Altistart 48
Environment:
All serial numbers
Cause:
Drive is detecting an under load fault?
Resolution:
ULF is an under load fault. The fault is caused by parameter settings on the soft starter. In the PRO menu parameter ULL (Activation of motor under load) enables the under load detection. Parameter LUL (Motor underload threshold) set the percentage of torque for the underload detection. Parameter TUL (Motor underload time), set the time delay before ULL faults when the motor torque falls below LUL threshold.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.