How do you program an auto/manual or com via digital input on the ATV630 and ATV930 Process drives?
Issue:
Setup the Hand/Off/Auto on the ATV630/ATV930 Process drives.
Product Line:
Altivar ATV630 ATV930 Process drive
Environment:
All
Cause:
Wants to be able to wire in an HOC or HOA for switching between the hand of auto or hand-off communications.
Resolution:
This programming is done in the Command and Reference menu. (Main Menu -> Complete Settings -> Command and Reference)
Ref Freq 1 and Cmd Channel 1 will apply to the low (deactivated) state of the switching digital input being used.
Ref Freq 2 and Cmd Channel 2 will apply to the high (activated) state of the switching digital input being used.
Example 1 hand off auto with terminal start stop control in both modes.
Ref Freq 1 config = AI1 for hand control or Pot
Control mode= not separate
Freq switch assign= DI3 logic is DI3 = low = hand or DI3= high= Auto
Ref Freq 2 Config= AI3 for auto control 4-20mA
Example 2 hand-off com
Ref Freq 1 config = AI1 for hand control or Pot
Control mode= I/O Profile
CMD switching = DI3
CMD channel 1= terminal mode
CMD channel 2 = Ethernet
Freq switch assign= DI3
Ref Freq 2 Config= Ethernet
Logic = DI3= low Pot speed and terminal control or DI3= high Ethernet command and speed reference.
Setup the Hand/Off/Auto on the ATV630/ATV930 Process drives.
Product Line:
Altivar ATV630 ATV930 Process drive
Environment:
All
Cause:
Wants to be able to wire in an HOC or HOA for switching between the hand of auto or hand-off communications.
Resolution:
This programming is done in the Command and Reference menu. (Main Menu -> Complete Settings -> Command and Reference)
Ref Freq 1 and Cmd Channel 1 will apply to the low (deactivated) state of the switching digital input being used.
Ref Freq 2 and Cmd Channel 2 will apply to the high (activated) state of the switching digital input being used.
Example 1 hand off auto with terminal start stop control in both modes.
Ref Freq 1 config = AI1 for hand control or Pot
Control mode= not separate
Freq switch assign= DI3 logic is DI3 = low = hand or DI3= high= Auto
Ref Freq 2 Config= AI3 for auto control 4-20mA
Example 2 hand-off com
Ref Freq 1 config = AI1 for hand control or Pot
Control mode= I/O Profile
CMD switching = DI3
CMD channel 1= terminal mode
CMD channel 2 = Ethernet
Freq switch assign= DI3
Ref Freq 2 Config= Ethernet
Logic = DI3= low Pot speed and terminal control or DI3= high Ethernet command and speed reference.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.