Issue:
Program ATV212 to follow the ACC and DEC set times.
Product Line:
Altivar 212
Environment:
ACC/DEC times
Cause:
N/A
Resolution:
Go into AUF (hit mode).
Arrow down to AU1 and change value from 1 to 0.
Set the ACC and DEC to the desired ramp up and ramp down times.
Program ATV212 to follow the ACC and DEC set times.
Product Line:
Altivar 212
Environment:
ACC/DEC times
Cause:
N/A
Resolution:
Go into AUF (hit mode).
Arrow down to AU1 and change value from 1 to 0.
Set the ACC and DEC to the desired ramp up and ramp down times.
Опубліковано для: Schneider Electric Україна

