Video: How do I program and wire an ATV212 to run using 3-wire control?
Configuring Altivar 212 Drives for 3-Wire Control
Product Line:
Altivar Buildings 212
Cause:
Need to use 3-wire (momentary) control
Resolution:
Programming:
Press MODE key to AUF
Arrow down to F---, and press ENT key
Set F111 to 2
Set F112 to 49
Wiring:
Wire the F terminal from a Normally Open (NO), momentary close, START contact
Wire the R terminal from a Normally Closed (NC), momentary open, STOP contact
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.