Control Expert (formerly Unity Pro) error message: "Exchange list generation fail : Code generation failure"

Article available in these languages: Spanish

Issue:
The user is editing online and receives the error and cannot proceed with a "Build changes" or "Rebuild All Project".

Environment:
Control Expert/Unity Pro software online with a PLC.

Resolution:
A change has been made that should be made in offline mode.
It requires disconnecting and performing a "Rebuild All" followed by a download.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.