Чим ми можемо вам допомогти сьогодні?

Control Expert (formerly Unity Pro) error message: "Exchange list generation fail : Code generation failure"

Article available in these languages:

  • Spanish

Issue:
The user is editing online and receives the error and cannot proceed with a "Build changes" or "Rebuild All Project".

Environment:
Control Expert/Unity Pro software online with a PLC.

Resolution:
A change has been made that should be made in offline mode.
It requires disconnecting and performing a "Rebuild All" followed by a download.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings