Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
How can I tell if my ATV61 or ATV71 drive is in sleep mode? (Low speed timeout active).
Issue:
Identify if an ATV61 or ATV71 drive is in sleep mode

Product Line:
ATV61 / ATV71 series drives.

Environment:
All models, All serial numbers

Cause:
Information not available in current literature.

Resolution:
A relay or logic output can not be configured to show this status.  In order to determine if the drive is in sleep mode, you will need to have a serial communication network connected to the drive.  Perform a read of parameter LRS3 (Logic address 3252 , 16#0CB4).  Bit 9 of this word will indicate whether the drive is asleep or awake.  If bit 9 is high, the drive is in sleep mode.  If low, the drive is in normal operation mode.

Also note that if the Low speed is set greater than 0Hz, the VFD status is RUN, and the VFD motor frequency is 0Hz, then the VFD is most likely in Sleep mode.

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Спільнота Schneider Electric
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings