How to configure audible alarms as per different alarm priorities in Vijeo Citect?

Follow below mentioned steps to configure different audible alarms as per alarm priorities.

1. In Citect Project editor open Computer setup editor > under Alarm group add sound<n> parameter.  Browse and select the sound file (in .wav format) as per alarm priority.  Add sound<n>Interval in Ctect.ini. Same way different sound files can be configured as per different alarm priorities.

In Citect Project editor open Computer setup editor

2. Define alarm priority as per different alarm categories.

Define alarm priority as per different alarm categories.

3. Then go to Citect project Editor > Systems > Included Projects and add CSV_Include project.

dd CSV_Include project.

4. Run computer setup wizard and in the Events setup enable CSV_AlarmClient. Then complete the wizard and start runtime.

Run computer setup wizard and in the Events setup enable CSV_AlarmClient.

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings