Clicking on the Settings link on the Power Monitoring Expert main page pops up an error window
Issue
When I use clicks on the "Settings" link on the Power Monitoring Expert main page a new error window pops up with link to GeneralSettingsDialog.html not found
Product
Power Monitoring Expert 8.1
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Main web site is using non default address like /PQweb instead of the default /web
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).*
1) Navigate to [PME install]\Applications\ApplicationFramework\content
2) Backup the file GeneralSettingsDialog.js
3) Edit the original file with a text editor
Replace the line TemplateUtil.LocAndLoad('/Web/Content/GeneralSettingsDialog.html', with the correct with the setup URL
For example
TemplateUtil.LocAndLoad('/PQWeb/Content/GeneralSettingsDialog.html',
4) Close all web clients and restart IIS
5) Verify that the link now opens the settings page.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.