Why does the ATV630 drive not save parameters when programmed over Modbus RTU?
ATV630 drive does not save parameters when programmed over Modbus RTU.
Product Line:
Altivar 630, Process
Environment:
All
Cause:
N/A
Resolution:
Modbus register value 8504 (CMI) will need to be written to in order for the drive parameters to be saved over the network.
CMI
Bit 0: Factory setting command (active at 1).
Bit 1: Save configuration to EEPROM non-volatile memory command (active at 1).
This Bit automatically changes to 0 after the request is taken into account. The command is only active if the drive is stopped, and not in "5-Operation enabled" state.
Bit 2: Reserved (= 0).
Bit 3: Reserved (= 0).
Bit 4: Reserved (= 0).
Bit 5: Reserved (= 0).
Bit 6: Reserved (= 0).
Bit 7: Reserved (= 0).
Bit 8: Reserved (= 0).
Bit 9: Definition of the frequency reference (LFr) and output frequency (rFr) unit:
= 0: 0.1 Hz
Bit 10: Reserved (= 0).
Bit 11: Reserved (= 0).
Bit 12: Reserved (= 0).
Bit 13: Reserved (= 0).
Bit 14: Reserved (= 0).
Bit 15: Parameter consistency check
Опубліковано для: Schneider Electric Україна




Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.