Чим ми можемо вам допомогти сьогодні?
Can I connect more than one Coordinator to the NetBotz Rack Monitor 250 wireless sensor network?
Issue
Each wireless sensor network must have one and only one Coordinator, connected only to the designated Wireless port on the Rack Monitor 250.
The Coordinator for the wireless sensor network on the NetBotz Rack Monitor 250 is under a plastic cover, connected to the port labeled Wireless. This is the only Coordinator allowed on the wireless sensor network.
Connecting an additional Coordinator to any other USB port on the appliance disables the Coordinator connected to the Wireless port.
Product Line
NetBotz Rack Monitor 250
Environment
NetBotz Rack Monitor 250
NetBotz USB Coordinator & Router
Cause
A firmware issue allows the Coordinator to enumerate when it is connected to a USB port other than the designated Wireless port.
Resolution
Use the Coordinator connected to the Rack Monitor 250 Wireless port as the only Coordinator on the wireless sensor network.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.