Issue
Alarms are not coming into ENM or the Refresh Tags will not show the PME OPC server in the refresh tags
Product Line
Event Notification Module 8.3.1
Environment
Power Monitoring Expert 8.1 or Power Scada Expert 8.1
Cause
There was an issue with the new alarm proxy interfacing properly with the Event Notification Module
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
The ENM Patch below will upgrade ENM 8.3.1 to 8.3.2, which will resolve the issue. This patch only applies to ENM 8.3.1 and PME 8.1.
Alarms are not coming into ENM or the Refresh Tags will not show the PME OPC server in the refresh tags
Product Line
Event Notification Module 8.3.1
Environment
Power Monitoring Expert 8.1 or Power Scada Expert 8.1
Cause
There was an issue with the new alarm proxy interfacing properly with the Event Notification Module
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
The ENM Patch below will upgrade ENM 8.3.1 to 8.3.2, which will resolve the issue. This patch only applies to ENM 8.3.1 and PME 8.1.
Опубліковано для: Schneider Electric Україна


Потрібна допомога?
Інструмент вибору продукту
Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.
Розрахувати вартість
Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Довідковий центр
Знайдіть усі необхідні ресурси для підтримки в одному місці.