What is the syntax / URL / script for opening directly an object from PLC application program accessible via webpage of BMENOC0311
The program viewer information should be enabled in the Unity application under tools > Projects Settings > PLC Diagnostics.
The firmware loaded in BMENOC0311 should be equal or above V2.07
The syntax / URL / Script is as follows
http://{IP_ADDRESS.EN_US}/#monitoring/plcpv?showConsole=0&showTreeview=0§ion=Section_Name|Object_Name&standalone=1
Where IP_ADDRESS is the IP address of BMENOC0311.
SECTION_NAME is the name of the section used in the PLC program
OBJECT_NAME is the name of the variable used in the ladder logic program and is the object identifier in case of the FBD program
The firmware loaded in BMENOC0311 should be equal or above V2.07
The syntax / URL / Script is as follows
http://{IP_ADDRESS.EN_US}/#monitoring/plcpv?showConsole=0&showTreeview=0§ion=Section_Name|Object_Name&standalone=1
Where IP_ADDRESS is the IP address of BMENOC0311.
SECTION_NAME is the name of the section used in the PLC program
OBJECT_NAME is the name of the variable used in the ladder logic program and is the object identifier in case of the FBD program
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.