Video: How do we export Alarm Group data from one project to another project in Vijeo Designer?

Issue:
How do we export Alarm Group data from one project to another project in Vijeo Designer?

Product Line:
Vijeo Designer (all versions)

Resolution:
To export alarm group data from one project to another project in Vijeo Designer, follow this procedure:

1) Ensure both the new and old application have an alarm group with same name
2) In the old application, goto variables in the navigator window and right-click. Choose "Export Variables"
3) Save the variable csv file somewhere on your PC
4) On the new application, goto variables in the navigator window and right-click. Choose "Import Variables"
5) Find the csv file on your PC and press the open button.

This will bring your alarm data into the new project.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings