Чим ми можемо вам допомогти сьогодні?
How do I configure my ATV212 series drive for Apogee communication?
Issue:
Configuring ATV212 series drive for Apogee communication.
Product Line:
ATV212 series drives
Environment:
All models where Apogee communication is in use.
Cause:
Information unclear in current literature.
Resolution:
Basic parameters are as follows:
F807 - Com channel choice - 0 for RJ45 port, 1 for 4 pin terminal block.
F829 - Network protocol, Set to 3 for Apogee (1- Modbus, 2-Metasys, 4-Bacnet *5-Lonworks. Note that an option card is necessary for Lonworks communication. All other options are built into the default control card of the drive)
F890 - Network Address (1 to 99)
F891 - Baud rate (0-9600, 1=4800, 2=9600, 3=19200, 4=76800, 5=57600, 6=76800)
F892 - Network timeout in 10ths. of a second. set to 100 (10.0 seconds) default. Range = 2 to 60 seconds.
The above settings are for monitoring only. If you wish to control via the Apogee network you must also make the following changes:
CMOD = 2 (switches start/stop control to the network. 0 = logic inputs, 1 = HMI, 2 = Serial communication).
FMOD = 4 (switches frequency reference to the network. 1 = VIA, 2 = VIB, 3 = Keypad, 4 = Serial communication, 5 = +/- speed via logic input.
Configuring ATV212 series drive for Apogee communication.
Product Line:
ATV212 series drives
Environment:
All models where Apogee communication is in use.
Cause:
Information unclear in current literature.
Resolution:
Basic parameters are as follows:
F807 - Com channel choice - 0 for RJ45 port, 1 for 4 pin terminal block.
F829 - Network protocol, Set to 3 for Apogee (1- Modbus, 2-Metasys, 4-Bacnet *5-Lonworks. Note that an option card is necessary for Lonworks communication. All other options are built into the default control card of the drive)
F890 - Network Address (1 to 99)
F891 - Baud rate (0-9600, 1=4800, 2=9600, 3=19200, 4=76800, 5=57600, 6=76800)
F892 - Network timeout in 10ths. of a second. set to 100 (10.0 seconds) default. Range = 2 to 60 seconds.
The above settings are for monitoring only. If you wish to control via the Apogee network you must also make the following changes:
CMOD = 2 (switches start/stop control to the network. 0 = logic inputs, 1 = HMI, 2 = Serial communication).
FMOD = 4 (switches frequency reference to the network. 1 = VIA, 2 = VIB, 3 = Keypad, 4 = Serial communication, 5 = +/- speed via logic input.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.