Can you connect the Multi-loader to a VW3A1101 keypad to get the saved files?
Issue:
Can you connect the Multi-loader to a VW3A1101 to get the saved files?
Product line:
VW3A8121, VW3A1101
Environment:
all
Cause:
Manual for the Multi-loader shows you can connect the device to the VW3A1101 keypads.
Resolution:
The connection is shown for the purpose of flashing an update to the keypad firmware using the VW3A8121 Multi-Loader.
The program files that are stored on the VW3A1101 cannot be loaded to the Multi-Loader because the format is different.
Can you connect the Multi-loader to a VW3A1101 to get the saved files?
Product line:
VW3A8121, VW3A1101
Environment:
all
Cause:
Manual for the Multi-loader shows you can connect the device to the VW3A1101 keypads.
Resolution:
The connection is shown for the purpose of flashing an update to the keypad firmware using the VW3A8121 Multi-Loader.
The program files that are stored on the VW3A1101 cannot be loaded to the Multi-Loader because the format is different.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.