PME - Too many registers exposed in Micrologic X driver to EWS
Issue
In PME8.2 and previous versions
1. Too many registers exposed in Micrologic X driver (in this file only 66 measurements have been exposed similar to legacy Micrologic drivers)
2. IONReferenceName and MeasurementName attributes and not aligned MM_MeasurementMap and PDM labels respectively
Environment
EWS service
Resolution
1. Replace the Types.Measurements_MicrologicX file in C:\Program Files(x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\Extensions
2. Update the EWS server in Management console
In PME8.2 and previous versions
1. Too many registers exposed in Micrologic X driver (in this file only 66 measurements have been exposed similar to legacy Micrologic drivers)
2. IONReferenceName and MeasurementName attributes and not aligned MM_MeasurementMap and PDM labels respectively
Environment
EWS service
Resolution
1. Replace the Types.Measurements_MicrologicX file in C:\Program Files(x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\Extensions
2. Update the EWS server in Management console
Опубліковано для: Schneider Electric Україна
Вкладення
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.