How to reset the Digital Input count on a CM2000
Issue
Customer would like to reset the digital input status counter on the CM2000.
Product Line
CM2000 series
Environment
Modbus Register writes
Cause
The CM2000 does not have a digital input status counter reset command.
Resolution
Using Modbus Tester, write a value of zero (0) to the desired registers. Below is an excerpt of the CM2000 Modbus Register list that details the Digital Input's registers.
| Registers | Range | |
|---|---|---|
| Input 1 Count | 2404 - 2405 | 0 to 99,999,999 |
| Input 2 Count | 2409 - 2410 | 0 to 99,999,999 |
| Input 3 Count | 2414 - 2415 | 0 to 99,999,999 |
| Input 4 Count | 2419 - 2420 | 0 to 99,999,999 |
| Input 5 Count | 2424 - 2425 | 0 to 99,999,999 |
| Input 6 Count | 2429 - 2430 | 0 to 99,999,999 |
| Input 7 Count | 2434 - 2435 | 0 to 99,999,999 |
| Input 8 Count | 2439 - 2440 | 0 to 99,999,999 |
In the following example, a CM2350's Input 1 Count is going to be reset. The necessary parameters are as follows:
- Gateway IP Address: 10.167.244.21
- CM2350 Device ID: 9
- Starting Register: 2404
Once all the parameters have been specified, press Write to reset the value.
Опубліковано для: Schneider Electric Україна


Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.