Issue:
Analog input setup on the ATV630 and ATV930 for a current 0 to 20mA signal
Product Line:
ATV630 ATV930
Environment:
All
Cause:
Wants to set up AI1 for 0 to 20mA for speed control
Resolution:
Setting up AI1 as a 0 to 20mA input.
Using the HMI display
Go to the Main Menu
Go to the Complete settings
Go to the Inputs and outputs
Choose the 3rd function key black tab AI/AO
Go to the AI1 configuration
Go to AI1 type
Choose Current
Set AI1 min value to 0mA
Set AI1 Max value to 20mA.
Programming manual link
https://www.se.com/us/en/download/document/EAV64318/