How can you read the PTH Power On Time status word parameter on the ATV660 drive over Ethernet?

Issue:
Reading the PTH Power On Time status word parameter on the ATV660 drive over Ethernet.

Product Line:
ATV660 and ATV960 drive

Environment:
All

Cause:
Wants to read the power on time PTH parameter in the input scanner map

Resolution:
You have to insert the PTH value in Somove using right click on the input table
and insert the PTH value. ( see the attachment file example).

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Вкладення
1CC36AE3AC93466C.jpg [101.11 KB]
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings