How can I connect an external enable/disable input to my Tesys LTMR Starter?
Issue:
Customer needs to connect an external "run permissive" input to the LTMR to use as an external shutdown interlock.
Product Line:
Overload Relays
Environment:
Tesys LTMR Motor Starters
Cause:
Function clarification needed.
Resolution:
I.3 input can be used as an 'external ready' input. This function is disabled by default and must be enabled in the LTMR via Somove programming or on the keypad. This function can also be enabled / disabled via serial communication at register 1250. Bit 1 enables/disables this function. Bit 0 and bit 2-15 of this register are reserved and should never be altered.
Customer needs to connect an external "run permissive" input to the LTMR to use as an external shutdown interlock.
Product Line:
Overload Relays
Environment:
Tesys LTMR Motor Starters
Cause:
Function clarification needed.
Resolution:
I.3 input can be used as an 'external ready' input. This function is disabled by default and must be enabled in the LTMR via Somove programming or on the keypad. This function can also be enabled / disabled via serial communication at register 1250. Bit 1 enables/disables this function. Bit 0 and bit 2-15 of this register are reserved and should never be altered.
Опубліковано для: Schneider Electric Україна
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.