McAffee Antivirus might detect a false positive trojan when scanning the file “xlMicrologic.dll” located at C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\bin\
Question:
PME8.2 Systems running on a system with McAfee might be affected by following issue.
McAffee Antivirus might detect a false positive trojan when scanning the file “xlMicrologic.dll” located at C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\bin\
This is the error that is seen in the windows log when the file is deleted:
"The file C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\bin\xlMicrologic.dll contains GenericRXEI-NB!D7D1FE14DE2E Trojan. The file was successfully deleted.
Confirmed McAffeeVersions affected
From DAT version: 8838.0000 to DAT version: 8844.0000
Issue has been reported to McAffee Support and they have confirmed that the issue is NOT present in DAT Version:8846.0000 (https://kc.mcafee.com/corporate/index?page=content&id=KB85567)
Please ask customer to deploy last update for antivirus and make sure is DAT Version:8846.0000 or higher
Cause:
False positive detected by specific version of McAffe. From DAT version: 8838.0000 to DAT version: 8844.0000
Resolution
Source:
the "xlMicrologic.dll" file
located at "C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\bin".
Version: 8.2.17055.2
- Please talk to customer to see I their McAffee is running DAT Version:8846.0000 or higher version
- Once they run with higher version, please ask their IT support to scan the file. (I would suggest different location on server for first check)
- Once the file passes the Scan on their server, then stop ION Services and place the file in the native location "C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\bin".
- Make sure the digital signature is preserved, and then start the ION services.
If something goes wrong in the process, please get the Windows Eventlogs (Source> McLogEvents), PME diag file, if possible the McAffee logs and feedback about the signature of the micrologic file, and contact technical support.
Опубліковано для: Schneider Electric Україна
Вкладення
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.